The goal of i.CanDoIt® is to provide a simple and cost effective facility management and remote monitoring solution suitable for use in small sites. i.CanDoIt®
includes data logging, time & date scheduling, and template or rule
based alarm processing with email notification and/or I/O activation in
response to events. Data logging simply records the contents of
registers on a user specified schedule. Event logging keeps a record of
alarm events. Scheduling causes register values to be set according to
a schedule. The resulting register manipulation may generate network
communication with remote devices, control local I/O, or change
setpoints. The i.CanDoIt® is programmable, even though it is rather powerful without programming.
Control Solutions’ i.CanDoIt® AMJR-14-IP
hardware features 12 inputs which accept analog input from thermistors
or 0-10V sensors, or discrete input from dry contact switches. AMJR-14
also provides 2 discrete outputs which can sink 1A at 24VDC.
Input
data is presented in scaled integer and floating point format.
Linearization tables are provided for 10K and 20K type II, III, and IV
thermistors on analog inputs. Input and output type and scaling are
configured in web pages served by the internal web server.
• 12 Analog/universal inputs
- - - 0-10VDC, Thermistor, dry contact
- - - Software selectable input type
- - - 10-bit resolution
- - - 2 channels capable of pulse count input
• 2 Discrete outputs
- - - Open drain FET, 1A current sink
• Modbus RTU Gateway Built In
• 10/100BaseT Ethernet
- - - Modbus TCP, SNMP, HTTP, email
• Data and event logger, email & trap notifications
• Real time scheduler including astronomical clock
• Web interface including user HTML wrapper & CGI
• User programmable via PL/i
• Powered by 10-30VDC or 24VAC 50/60 Hz
• Power Consumption:
- - - 0.3A @ 24VDC max.
• DIN rail mounting, 100mm Hx70mm Wx60mm D
• Pluggable screw terminal blocks
• Operating temperature -40°C to +85°C
• Humidity 5% to 90%
• FCC Class B, CE Mark |