The goal of i.CanDoIt® is to provide a simple and cost effective facility management and remote monitoring solution suitable for use in small sites. i.CanDoIt®
includes data logging, time & date scheduling, and template or rule
based alarm processing with email notification and/or I/O activation in
response to events. Data logging simply records the contents of
registers on a user specified schedule. Event logging keeps a record of
alarm events. Scheduling causes register values to be set according to
a schedule. The resulting register manipulation may generate network
communication with remote devices, control local I/O, or change
setpoints. The i.CanDoIt® is programmable, even though it is rather powerful without programming.
The Modbus version of the i.CanDoIt® server features a Modbus RTU Master and Modbus TCP Client and Server. This
server is ideal for systems based entirely on Modbus. The server will
support polling of up to 50 RTU slaves, and IP connections with 25
TCP/IP devices. The i.CanDoIt® server as a Modbus controller is freely programmable.
Control Solutions’ AddMe III features 18 universal inputs which are context sensitive. When configured as an analog input, the continuously self-calibrating
sigma-delta converter produces 15-bit resolution with high noise
immunity. When configured as a discrete input, the converter switches
to 8-bit resolution at 128 samples per second for fast response.
Data
is presented in scaled integer and floating point format. Linearization
tables are provided for 10K and 20K type II, III, and IV thermistors on
analog inputs. Input and output type and scaling are configured in web
pages served by the internal web server.
• 18 Analog/universal inputs
• 0-10VDC, Thermistor, dry contact
• Software selectable input type
• 0.1% reference, up to 16-bit resolution
• Continuously self-calibrating sigma-delta converter
• 4 Analog outputs
• 4-20mA (0-20mA)
• 8-bit resolution
• 8 Discrete outputs
• Form A relay, 5A @ 120VAC
• HOA switches & LED status indicators
• 2 Pulse/Discrete inputs
• TTL to 24VDC
• Rate or totalizing count input
• Modbus RTU Gateway Built In
• Modbus RTU master handles up to 50 slaves
• 10/100BaseT Ethernet
• Data and event logger, email & trap notifications
• Real time scheduler including astronomical clock
• Web interface including user HTML wrapper
• User programmable using PL/i
• Powered by 18-30VDC or 24VAC 50/60 Hz
• Power Consumption: 0.3A @ 24VDC max.
• DIN rail mounting, 100mm H x 155mm W x 60mm D
• LED indicators for power, status, Tx/Rx, comm error
• Pluggable screw terminal blocks
• Operating temperature -40°C to +70°C
• Humidity 5% to 90%
• FCC Class A, CE Mark |