Control Solutions AddMe Lite
features 12 inputs which accept analog input from thermistors or 0-10V
sensors, or discrete input from dry contact switches. AddMe Lite also
provides 2 discrete outputs which can sink 1A at 24VDC.
Analog
Input objects provide data from the analog I/O points. Linearization
tables are provided for 10K and 20K type II, III, and IV thermistors.
Input type and scaling is configured by writing to object properties.
Binary Output objects provide BACnet access to the outputs. An
additional 60 writeable Multistate Input objects are available for use
by the user's program.
12 Analog/universal inputs
- - - 0-10VDC, Thermistor, dry contact
- - - Software selectable input type
- - - 10-bit resolution
- - - 2 channels capable of pulse count input
2 Discrete outputs
- - - Open drain FET, 1A current sink
BACnet MS/TP Slave
Supports 9600, 19200, 38400, 76800 baud
Powered by 10-30VDC or 24VAC 50/60 Hz
Power Consumption:
- - - 0.15A @ 24VDC max.
DIN rail mounting, 100mm H x 70mm W x 60mm D
Pluggable screw terminal blocks
Operating temperature -40°C to +85°C
Humidity 5% to 90%
FCC Class B, CE Mark
Objects Provided
40 Analog Input (20 uncommitted, writeable)
2 Binary Output (commandable)
60 Multistate Input (60 uncommitted, writeable)
1 Device
2 File
1 Program |