Babel Buster 485
is a fully configurable universal LonWorks to Modbus RTU gateway. The
RTU master is used to make Modbus RS-485 devices accessible on a
LonWorks network. The RTU slave is used to make LonWorks devices
accessible on a Modbus RS-485 network. The Babel Buster 485 gateway is
designed to be economical enough to use multiple gateways, one per
device or group of devices, rather than run parallel networks to a
larger, more expensive gateway.
An
RTU master Babel Buster 485 can poll multiple Modbus slaves, and can be
bound to any number of LonWorks devices. An RTU slave Babel Buster 485
responds to a single Modbus slave unit ID, and may be bound to any
number of LonWorks devices. LonWorks network variable data is
translated to Modbus register data, and vice versa. Modbus polling
rates and LonWorks network update rates are fully configurable.
Register mapping and network variable types (SNVT) are fully
configurable.
The
LonMark Certified Babel Buster 485 conforms fully to LonMark version
3.3. The only tool required to configure Babel Buster is LonMaker
version 3.
Universal, fully configurable
You pick the Modbus register
You pick the SNVT type
No extra software or drivers to buy
LonWorks TP/FT-10 (FTT-10A) to Modbus RS-485 Gateway
Translate 58 LonWorks variables to Modbus registers
LonMark Ver. 3.3 Sensor & Actuator Functional Profiles
Modbus coils, input registers, holding registers
Single or double Modbus registers
Signed, unsigned, IEEE 754
All scalar LonMark SNVT types supported
SNVT_switch & SNVT_state also supported
SNVT types dynamically assignable via LonMaker
Modbus registers dynamically mappable via LonMaker
Modbus registers may be scaled (x10, x0.1, etc.)
Min/max send time, send on delta configurable per point
Modbus (master) polling interval configurable per point
Object override supported on point by point basis
Bidirectional communication between LonWorks & Modbus
LonMark certified, version 3.3
3150L Neuronฎ Chip, 48K Flash memory, 10K RAM
TP/FT-10 (FTT-10A) transceiver
Powered by 10-30VDC or 12-24VAC 50/60 Hz
Power Consumption: 0.1A @ 24VDC
DIN rail mounting, 100mm H x 70mm W x 60mm D
LED indicators for LonWorks & Modbus status
Pluggable screw terminal blocks
Operating temperature -40ฐC to +85ฐC
Humidity 5% to 90%
FCC Class B, CE Mark |