Babel Buster 10/100
is a fully configurable universal LonWorks to Modbus/TCP gateway. The
Modbus master is used to make Modbus/TCP devices accessible on a
LonWorks network. The Modbus slave is used to make LonWorks devices
accessible on a Modbus/TCP network.
As
a Modbus master (client), Babel Buster 10/100 can poll multiple Modbus
slave IP addresses, and can be bound to any number of LonWorks devices.
As a Modbus slave (server), Babel Buster 10/100 responds to a single IP
address, and may be bound to any number of LonWorks devices.
Babel Buster 10/100 operates as both client and server concurrently,
with master and slave functionality enabled on an object by object
basis.
LonWorks
network variable data is translated to Modbus register data, and vice
versa. Modbus polling rates and LonWorks network update rates are fully
configurable. Register mapping and network variable types (SNVT) are
fully configurable.
The
LonMark Certified Babel Buster 10/100 conforms fully to LonMark version
3.3. The only tool required to configure Babel Buster is LonMaker
version 3.
Universal, fully configurable
You pick the Modbus register
You pick the SNVT type
No extra software or drivers to buy
LonWorks TP/FT-10 (FTT-10A) to Modbus/TCP Gateway
Auto-sensing 10BaseT/100BaseT Ethernet
Static IP assigned from LonMaker, or BOOTP/DHCP
Translate 58 LonWorks variables to Modbus registers
LonMark Ver. 3.3 Sensor & Actuator Functional Profiles
Modbus coils, input registers, holding registers
Single or double Modbus registers
Signed, unsigned, IEEE 754
All scalar LonMark SNVT types supported
SNVT_switch & SNVT_state also supported
SNVT types dynamically assignable via LonMaker
Modbus registers dynamically mappable via LonMaker
Modbus registers may be scaled (x10, x0.1, etc.)
Min/max send time, send on delta configurable per point
Modbus (master) polling interval configurable per point
Object override supported on point by point basis
Bidirectional communication between LonWorks & Modbus
LonMark certified, version 3.3
3150L Neuronฎ Chip, 48K Flash memory, 10K RAM
TP/FT-10 (FTT-10A) transceiver
Powered by 10-30VDC or 12-24VAC 50/60 Hz
Power Consumption: 0.1A @ 24VDC
DIN rail mounting, 100mm H x 70mm W x 60mm D
10BaseT/100BaseT standard RJ-45 connector
LED indicators for LonWorks, Modbus, Ethernet link status
Pluggable screw terminal blocks
Operating temperature -40ฐC to +85ฐC
Humidity 5% to 90%
FCC Class B, CE Mark |